joint or union using a small paintbrush. If any bubbling is
observed, the connection is not sealed adequately and
must be retightened. Repeat the tightening and soap
check process until bubbling ceases.
IMPORTANT NOTE: When pressure testing gas supply
lines at pressures greater than 1/2 psig (14 inch W.C.),
the gas supply piping system must be disconnected
from the furnace to prevent damage to the gas control
valve. If the test pressure is less than or equal to 1/2
psig (14 inch W.C.), close the manual shut-off valve.
required that you measure the gas input rate. This may
be accomplished in the usual way, by clocking the gas
meter and using the local gas heating value. To check the
input of the furnace see page 21.
IMPORTANT NOTE: Observe the action of the burners
to make sure there is no yellowing, lifting or fl ashback
of the fl ame.
Converting to LP Gas
The CMF2 furnace is shipped from the factory for use with
natural gas but can be converted to use liquid propane
gas. Use the following procedure and Figure 12 (page 17)
for converting the gas burner.
1. Set thermostat to OFF.
2. Turn off all power to the furnace.
3. Open furnace door and locate the gas valve.
4. Push in on the gas knob and turn it to OFF.
5. Shut off gas supply at meter.
6. Disconnect gas burner electric cord, gas piping to
burner, and thermostat leads.
7. Remove nuts securing burner in place.
8. Disconnect inlet pipe union at burner.
9. Disconnect the two wires leading to gas control valve.
10. Remove bolts securing U-shaped manifold plate to
orifi ce assembly.
11. Remove the main orifi ce and replace it with the correct
LP fuel orifi ce as shown in Table 4. Refer to the rating
plate on the furnace to determine the fi ring rate for
your application. NOTE: If the fi ring rate of your furnace
has been converted, make sure the appropriate LP
orifi ce for the new fi ring rate is installed.
12. Remove the regulator converter on top of the gas valve.
Invert the converter so that the red ring will be located
at the bottom and the LP stamping on the converter
appears up.
13. Screw converter back into the regulator, hand tight
plus 1/8 turn.
14. Reinstall the burner assembly into the furnace.
15. Reconnect the gas piping and electrical wires to the
gas valve.
16. Open the manual shut-off valve and follow the Operating
Instructions outlined on page 20.
High Altitude Application
Installation of this furnace at altitudes above 2,000 feet
shall be in accordance with local codes, or in the absence
of local codes, the National Fuel Gas Code, ANSI Z223.1/
NFPA 54 or National Standard of Canada, Natural Gas &
Propane Installation Code CGA B149.1. Please consult
your local code authority.
WARNING:
The reduction of input rating necessary for high
altitude installation may only be accomplished
with factory supplied orifi ces. Do not attempt to
drill out orifi ces in the fi eld. Improperly drilled
orifi ces may cause fi re, explosion, carbon
monoxide poisoning, personal injury or death.
The CMF2 furnace is shipped from the factory with its
orifi ces and gas regulator setting for natural gas operation
at sea level altitudes. At 2,000 feet, the NFGC requires
that this appliance be derated 4% for each 1,000 feet of
altitude. For example, the input needs to be reduced 8%
at 2,000 feet, 12% at 3,000 feet, etc. This deration is in
reference to the input rate and gas heating value at sea
level.
High altitude conversion for this furnace requires reducing
the orifi ce size or decreasing the manifold pressure. When
decreasing the manifold pressure, the pressure must not
be set below 3.2 in WC. If the pressure needs to be set
below 3.2 in WC to achieve proper deration, then change
the orifi ce size and raise the manifold pressure back to
3.5 in WC.
After changing the regulator pressure or the orifi ces, it is
* Times are based on natural gas at an average of 1,000 BTU per cubic foot, a burner manifold pressure of 3.5 in WC, and a meter dial size of 1 cubic foot.
** Times are based on LP gas at an average of 2,500 BTU per cubic foot, a burner manifold pressure of 3.5 in WC, and a meter dial size of 1 cubic foot.
Table 4. Natural & LP Gas Orifi ces
Burner
Designation
Firing Rate
Input (BTUH)
Natural Gas
Orifi ce Number
Natural Gas
Time Per Rev.* (sec)
LP Gas
Orifi ce
Number
LP Gas
Time Per Rev.** (sec)
Gas Gun-65-DI-S 65,000 24 55 43 138
Gas Gun-75-DI-S 75,000 20 48 40 120
Gas Gun-90-DI-S 85,000 18 43 37 106