4-7. Weld Output Cables
. For weld output cable replacements or extensions, contact your Factory Authorized Service Agent.
4-8. Electrical Service Guide
Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These recommenda-
tions are for a dedicated branch circuit sized for the rated output and duty cycle of the welding power source.
50/60 Hz Single
Phase
Input Voltage (V) 220 230
Input Amperes (A) At Rated Output [70]
47.5
[67]
Max Recommended Standard Fuse Rating In Amperes
1
Time-Delay Fuses
2
[90] 50 [80]
Normal Operating Fuses
3
[110] 70 [100]
Min Input Conductor Size In AWG
4
[8]
12
[10]
Max Recommended Input Conductor Length In Feet (Meters) [75 (23)]
87 (26)
[82 (25)]
Min Grounding Conductor Size In AWG
4
[8] 12 [10]
[ ] Electrical Service Requirements For 300/200 AC/DC And 300 AC Models
Reference: 2008 National Electrical Code (NEC) (including article 630)
1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 “Time-Delay” fuses are UL class “RK5” . See UL 248.
3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amps), and UL class “H” ( 65 amps and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.